ITS Service Status Report

Scheduled Maintenance

UPS annual Maintenance at Michigan Academic Computing Center

Services Affected: Data Center Services

Start Time: 09/21/2019 8:00 am

Anticipated End Time: 09/22/2019 5:00 pm

Issue Symptoms: None

Who is Impacted? none

None 

Next Update: 09-21-2019 @ 1:00 pm

Technical Details

Service Type: Production

Comments:

9/21/19 @ 11:00 am  Maintenance is progressing along with no issues.

9/21/19 @ 9:00 am Maintenance has started and moving along with no issues.

 

What we are doing: Eaton will be performing a complete battery resistant testing phase and will perform the annual preventative maintenance (PM) for the uninterruptible power system (UPS) and UPS battery string. Eaton will perform this on 1 (one) UPS at a time so the system as adequate backup in case of an event and is needed.

Why we are doing this: Annual maintenance allows us to see the longevity and life of the battery's. As well as the functionality of the UPS system.

Who will be impacted:  We anticipate no impact to any services running at Michigan Academic Computing Center. Eaton will perform the maintenance on 1 (one) UPS at a time to maintain adequate redundancy.

Groups Notified:

Report Additional Impacts